Keywords
|
convergent vortex tube, conical valve angle, injection
pressure, slots number, optimization
|
Abstract
|
Seven adjustments of convergent-type Vortex Tube (VT)
with different throttle angles were applied. The adjustments were
made to analyze the influences of such angles on cold and hot
temperature drops as well as flow structures inside the VTs. An
experimental setup was designed, and tests were performed on
different convergent VT configurations at injection pressures
ranging from 0.45 to 0.65 MPa. The angles of the throttle valve
were arranged between 30° to 90°, and the numbers of injection
nozzles ranged between 2 and 6. Laboratory results indicated that
the maximum hot and cold temperature drops ranged from 23.24 to
35 K and from 22.87 to 32.88 K, respectively, at four injection
nozzles. Results also showed that temperature drop is a function of
hot throttle valve angle with the maximum hot and cold
temperature drops depending on the angle applied. We used graphs
to demonstrate the changes in the cold and hot temperature drops
with respect to hot throttle angle values. These values were
interpreted and evaluated to determine the optimum angle, which
was 60°. The CFD outputs agreed very well with the laboratory
results. The proposed CFD results can help future researchers gain
good insights into the complicated separation process taking place
inside the VTs.
|