چکیده
|
In present study, a new heat pump named cascaded compression-absorption heat pump (CCAHP) is introduced,
thermodynamically analyzed and compared with that three other classes of heat pumps (compression,
absorption, and hybrid compression-absorption) with identical waste heat source. Ammoniawater
solution is used in the absorption as well as hybrid systems and pure ammonia in the compression
system. The simulations are performed in EES (Engineering Equation Solver) software. Low-grade heat is
externally supplied to the systems and upgraded heat is transferred to a medium with high temperature.
Comparison of the results shows that with increasing the temperature lifts, the PER (Primary energy
ratio) and second law efficiency of the cascaded system reach to the values of these parameters of the
compression system. Even at higher values of temperature lifts, that compression system cannot perform,
cascaded system operates with higher values of PER and second law efficiency compared to those of
hybrid compression-absorption system. Advantages of the proposed cascaded system are small value
of compression ratio, maximum pressure and exit temperature of the compressor comparing to the other
investigated cycles which extend the working domain of the cascaded system.
|