Novel control structure of single-phase active power filter using recursive least squares estimator considering a distorted environment
نوع پژوهش مقاله چاپ شده
کلیدواژه‌ها
Distorted environment, signal measurement, SOGI-FLL, VFF-RLS estimator
چکیده
In this paper, a new reactive power and harmonic compensation procedure based on the variable forgetting factor-recursive least squares (VFF-RLS) estimator and new phase-locked loop is proposed. For this purpose, the fundamental harmonic component of load current is estimated with VFF-RLS. Independence on order and amplitude of harmonics, fast dynamic and high accuracy are the remarkable features of the designed estimator. As in the case of load changes, the sag/swell and phase jump in grid voltage, optimal compensation is performed in less than half a cycle with a low total harmonic distortion value. In addition, to compensate for an infected power system by varied frequency, a second-order general integrator-frequency-locke d loop (SOGI-FLL) control system based on wavelet transform (WT) has been proposed. This phase detector can track the reference phase of a grid in the best manner in the presence of frequency variations. The effectiveness of the proposed method in a single-phase power system has been validated using both simulation and experimental results.
پژوهشگران مهدی فلاح (نفر اول)، حسین مددی (نفر دوم)، محمد توکلی بینا (نفر سوم)، علی عجمی اسفنگره (نفر چهارم)