کلیدواژهها
|
—DER, haar expansion, LVRT, transmission system
security, voltage sag.
|
چکیده
|
Low voltage ride through (LVRT) is a solution to
increase the tolerance of distributed energy resources (DERs)
against the voltage sags. However, the possibility of DERs trip
according to the present grid codes exists. Such trips do not have
a substantial local effect but are essential for transmission systems
with connected DER-penetrated distribution networks (DPDNs).
This paper investigates an analytical framework to see the impact of
distribution-level LVRT response on transmission system security.
LVRT response stands for the total amount of lost DER capacity due
to the inability to meet the LVRT requirement during the voltage
sag. This generation loss in the distribution sector can expose the
transmission network to lines overloading after fault clearance.
The proposed novel approach is based on a source contingency
analysis that lets transmission system operators (TSOs) conduct
an LVRT-oriented security assessment. In this kind of security
assessment, a mathematical function is defined as the LVRT
response function of DPDNs. This function gives the lost DER
capacity in response to the transmission-level transient faults and is
constructed by distribution system operators (DSOs). The TSO can
use these functions to assess the loading security of transmission
lines in post-clearance system conditions. In this analytical
framework, LVRT-oriented security is evaluated by calculating
the risk of lines overloading under a large number of random faults.
The proposed approach is implemented in two test power systems
with a considerable DER penetration level to obtain the risk of line
overloading due to the LVRT response in distribution networks.
|